ExitGlo50  Data

Product:

 
ExitGlo50 High Performance Photoluminescet Exit Sign. For indoor use only.
Safegaurds:
1. The sign must be charged for a minimum of 60 minutes to become fully operational.
2. External illumination source must be supplied by a circuit not controlled by an automatic timer or sensor and whose controls are accessible only to authorized personnel.
3. External illumination source is to be energized at all times during building occupancy.
4. Lighting levels on the sign face(s) should be confirmed after any change in external lighting.
5. It is recommended that inspections be performed in accordance with applicable codes.
6. Install sign indoors only, where not exposed to direct sunlight, moisture or temperatures outside the range of +10 degree to 40 C (50-104 F).
Activation:

C
aution Minimum 5 foot-candles (54 Lux of External Unfiltered Fluorescent Illumination must be present on the sign face at all times during occupancy).
Application: 
ExitGlo exit signs can be used as a primary or secondary exit sign in accordance with the UL924 standard for "Emergency Lighting and Power Equipment", Eighth Edition, July 2001 revisions. Install in compliance with NFPA Life Safety Code 101 or other applicaple buiding or fire codes for photoluminescent exit signs. They are non-explosive, non-corrosive,non-toxic, non-radioactive and non-electric, requiring no electrical wiring or batteries.

Certifications:
UL924 compliant for a maximum viewing distance of 50 feet.
Chevrons: 
Directional Chevrons are available in right, left or double configurations are permanent and must be pre-configured in advance.
Maintenance:

Maintenace of the Exit Sign is limited to periodic cleaning of the sign face and should be done with a non-abrasive soft cloth dampened with water. Do not use chemical solvants of any kind.